@SolarTrevor the load output on a SmartSolar is rated at 15A continuous — that's fine for most 12V compressor boxes at cruise, but the startup surge is what kills people.
Had this exact issue with my 100/30 last summer. Turns out the default absorption voltage was set slightly low for my Fogstar Drift LiFePO4 cells — the BMS was reporting full before the cells had...
@Nobby78 has covered negative earthing but let me add some precision here — in a DC-only standalone system the distinction between earthing and bonding matters enormously and gets confused...
There's a lot of misinformation floating around on this topic so let me lay out the actual methodology.
Start with your load, not your panels.
List every device, its wattage, and daily hours of...
Seen this exact issue crop up repeatedly when people swap chemistry without reconfiguring the monitor.
@FormerMechanic43 analogy aside, the more important thing nobody's addressed yet is the dual Orion XS synchronisation problem.
Two XS units on a single smart alternator output without proper...
@RetiredNurse49 has already covered the workaround but the root cause is worth nailing down properly.
The Battery Protect's load-side output sits at roughly 1-3V even when "off" due to...
@Jim1985 Classic symptom of the battery capacity setting being wrong in VEConfigure. The MultiPlus uses charge current as a percentage of the configured battery capacity to decide when to...
@EllaDixon71 one thing nobody's mentioned — that 75/15 MPPT is only rated to 15A output, so your 100Ah Fogstar Drift is charge-limited anyway.
Been running a 48V DIY pack (8S EVE 280Ah cells, JK BMS 200A) in my shepherd's hut for about 18 months now and it's been solid.
SolarNotSure | 2,156 posts | 🔋 Technically Opinionated
@StormyHiker something nobody's touched on yet: check your tail current threshold in VEConfigure.
@LisaKelly66 is on the right track but didn't finish the thought, so I will.
Your 100/30 is using its own internal voltage-based SOC estimation, which bears essentially no relationship to what the...
@Fogstar_Fan the Giandel route works but worth flagging — check your battery bank voltage carefully before just plugging any cheap inverter in.
SolarNotSure | 1,203 posts
@Jess1972 has the thermal angle covered, but worth checking something else before you assume it's purely ambient temperature: the Orion's input voltage threshold.
Once...
@Jock90 What BMS are you running and how is it connected to the Cerbo/CCGX? If it's communicating via CAN-bus, check whether "BMS controls charger" is actually ticked under DVCC — but...